Additional Information
Data sheet, technical information
1SDC210100D0206
1SDC210099D0206
E-number (sweden)
3182430
Eclass
V11.1 : 27370409
Package level 1 depth / length
143 mm
EAN
8015644013097
Product net depth / length
70
mm
Rohs status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Weee category
5. Small Equipment (No External Dimension More Than 50 cm)
Main
Product Name
Moulded Case Circuit Breaker
Product type
Automatic Circuit Breaker
version
F
Complementary
Declaration of conformity - ce
9AKK106713A5532
Opening time
CB with SOR 15 ms
CB with UVR 15 ms
Package level 1 gross weight
1.134 kg
Product net weight
1.1
kg
[in] rated current
80 A
Cad dimensional drawing
1SDH001295R0008
Conflict minerals reporting template (cmrt)
9AKK108467A5658
Etim 4
EC000228 - Power circuit-breaker for trafo/generator/installation prot.
Etim 5
EC000228 - Power circuit-breaker for trafo/generator/installation prot.
Package level 1 height
135 mm
Product net width
76.2
mm
[ics] rated service breaking capacity
(220 V AC) 50 kA
(230 V AC) 50 kA
(240 V AC) 50 kA
(380 V AC) 36 kA
(415 V AC) 36 kA
(440 V AC) 18 kA
(500 V AC) 15 kA
(525 V AC) 11 kA
(690 V AC) 5 kA
(250 V DC) 2 Poles in Series 36 kA
(500 V DC) 3 Poles in Series 36 kA
Package level 1 units
box 1 piece
Package level 1 width
128 mm
dimension
1SDH000719R0100
Environmental information
9AKK107991A8215
9AKK108467A6707
Instructions and manuals
1SDH000719R0001
Order code us and canada
XT1NE3080AFF000XXX
Order multiple
1 piece
Gl certificate
1SDL000163R0103
Minimum order quantity
1 piece
Product main type
SACE Tmax XT
mechanical durability
240 cycles per hour
25000 cycle
Object classification code
Q
electrical durability
120 cycles per hour
8000 cycle
Package level 1 ean
8015644013097
Product net height
130
mm
Rated frequency (f)
50 / 60 Hz
Rated uninterrupted current (iu)
160 A
Rated impulse withstand voltage (uimp)
8 kV
Rated insulation voltage (ui)
800 V
Rated voltage (ur)
690 V
Power loss
at Rated Operating Conditions per Pole 4.8 W
Release
TMD
Short-circuit performance level
N
Rated operational voltage
690 V AC
500 V DC
Rated instantaneous short-circuit current setting (ii)
800 A
Reach declaration
9AKK108466A1425
Sub-type
XT1
Poles description
3
Terminal connection type
Front
Wiring diagram
1SDM000068R0001
Ul certificate
No certification needed
Rated ultimate short-circuit breaking capacity (icu)
(220 V AC) 65 kA
(230 V AC) 65 kA
(240 V AC) 65 kA
(380 V AC) 36 kA
(415 V AC) 36 kA
(440 V AC) 36 kA
(500 V AC) 30 kA
(525 V AC) 22 kA
(690 V AC) 6 kA
(250 V DC) 2 Poles in Series 36 kA
(500 V DC) 3 Poles in Series 36 kA
Setting range
56...80 A
Environment
Atex certificate
No certification needed
Circuit breaker type to be associated
Power Distribution
Customs tariff number
85362090
Release type
TM
Current type
AC/DC
ETIM - 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Etim 6
EC000228 - Power circuit-breaker for trafo/generator/installation prot.
Mechanical drawings
1SDH000719R0100
standards
IEC
Etim 7
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Lr certificate
1SDL000163R0100
Scip
f628c62e-5364-4273-b02b-bc0e014f8c5e Italy (IT)
E-number (finland)
3640530
Rohs information
9AKK108466A1424
Toxic substances control act - tsca
9AKK108467A8326
Unspsc
39120000
Vde certificate
No certification needed