Complementary
Declaration of conformity - ce
1SCC301168D2702
Handle type
Knob
Handle and shaft not included
Package level 1 gross weight
0.52 kg
Product net weight
0.49
kg
Conflict minerals reporting template (cmrt)
9AKK108467A5658
Etim 5
EC000216 - Switch disconnector
Package level 1 height
109 mm
Position of line terminals
Top In - Bottom Out
Bottom In - Top Out
Product net width
96.5
mm
Cable cross section
Cu 10 ... 70 mm²
Country of origin
Finland (FI)
Distance between phases
Standard
Fourth pole position
Right Side
Package level 1 units
box 1 piece
Lock type
No
Package level 1 width
86 mm
tightening torque
acc. IEC 60947-1 6 N·m
Fourth pole type
Switched - Simultaneous Function
Environmental information
1SCC301264D0201
Horsepower rating ul/csa
(acc. to UL 200 V) 25 Hp
(acc. to UL 480 V) 50 Hp
(acc. to UL 240 V) 30 Hp
(acc. to UL 208 V) 25 Hp
(acc. to UL 600 V) 50 Hp
Idea granular category code (igcc)
5290 >> Disconnect switch
Instructions and manuals
1SCC301058M0008
Maximum operating voltage ul/csa
600 V
Minimum order quantity
10 piece
mechanical durability
20000
Object classification code
Q
Rated conditional short-circuit current (inc)
(125 A fuse, 415 V) 50 kA
(125 A fuse, 690 V) 10 kA
(63 A fuse, 690 V) 50 kA
Package level 1 ean
6417019391816
Pollution degree
3
Product net height
100
mm
Rated short-time withstand current low voltage (icw)
for 1 s 2.5 kA
Rated operational current ac-21a (ie)
(380 ... 415 V) 125 A
(500 V) 125 A
(690 V) 125 A
Rated impulse withstand voltage (uimp)
8 kV
Rated operational current ac-22a (ie)
(380 ... 415 V) 125 A
(500 V) 125 A
(690 V) 125 A
Rated insulation voltage (ui)
acc. to IEC/EN 60664-1 750 V
Rated operational current ac-23a (ie)
(380 ... 415 V) 90 A
(500 V) 70 A
(690 V) 50 A
Rated operational power ac-23a (pe)
(220 ... 240 V) 22 kW
(400 ... 415 V) 45 kW
(500 V) 45 kW
(690 V) 45 kW
Operating mode
Front operated
Rated short-circuit making capacity (icm)
(690 V) 3.6 kA
Power loss
at Rated Operating Conditions per Pole 6.3 W
Switches operating mechanism
Mechanism on Top of the Switch
Rated operational voltage
Main Circuit 750 V
Reach declaration
1SCC011021D0201
Poles description
4
Ul certificate
cULus certificate OT30-125
Environment
Ampere rating
100 A
Atex certificate
No certification needed
Conventional free-air thermal current (ith)
Θ = 40 °C 125 A
Customs tariff number
85365080
Conventional thermal current (ithe)
Fully Enclosed 125 A
ETIM - 8
EC000216 - Switch disconnector
Etim 6
EC000216 - Switch disconnector
Mechanical drawings
1SCC301468F0001
1SCC301467F0001
OT100-125F4N2.stp
OT100-125F4N2.igs
standards
IEC 60947-3
Etim 7
EC000216 - Switch disconnector
Etim 9
EC000216 - Switch disconnector (low voltage)
E-number (finland)
3601413
Rohs information
1SCC011020D0201
Unspsc
39122233
Vde certificate
No certification needed