Additional Information
Data sheet, technical information
1SCC301020C0201
E-number (sweden)
2102720
Eclass
V11.1 : 27371403
Package level 1 depth / length
103 mm
Product net depth / length
73
mm
Rohs status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Special functions
No
Weee category
5. Small Equipment (No External Dimension More Than 50 cm)
Main
Terminal type
Screw Terminals
Mounting type
Base mounting
degree of protection
Front IP20
Complementary
Declaration of conformity - ce
1SCC301166D2703
Handle type
Handle and shaft not included
Package level 1 gross weight
0.1 kg
Product net weight
0.09
kg
Conflict minerals reporting template (cmrt)
9AKK108467A5658
Etim 5
EC000216 - Switch disconnector
Package level 1 height
82 mm
Position of line terminals
Top In - Bottom Out
Bottom In - Top Out
Product net width
35
mm
Cable cross section
Cu 0.75 ... 10 mm²
Country of origin
Finland (FI)
Distance between phases
Standard
Package level 1 units
box 1 piece
Lock type
No
Package level 1 width
86 mm
tightening torque
acc. IEC 60947-1 0.8 N·m
Environmental information
1SCC301262D0201
Instructions and manuals
1SCC301052M0006
Minimum order quantity
1 piece
mechanical durability
20000
Object classification code
Q
Rated conditional short-circuit current (inc)
(40 A fuse, ≤415V) 50 kA
(25 A fuse, 690 V) 50 kA
Package level 1 ean
6417019158402
Pollution degree
3
Product net height
68
mm
Rated short-time withstand current low voltage (icw)
for 1 s 0.5 kA
Rated operational current ac-21a (ie)
(380 ... 415 V) 40 A
Rated impulse withstand voltage (uimp)
8 kV
Rated operational current ac-22a (ie)
(380 ... 415 V) 40 A
(500 V) 40 A
(690 V) 40 A
Rated insulation voltage (ui)
acc. to IEC/EN 60664-1 750 V
Rated operational current ac-23a (ie)
(380 ... 415 V) 23 A
(500 V) 23 A
(690 V) 12 A
Rated operational power ac-23a (pe)
(220 ... 240 V) 5,5 kW
(400 ... 415 V) 11 kW
(500 V) 11 kW
(690 V) 11 kW
Operating mode
Front operated
Rated short-circuit making capacity (icm)
(690 V) 0.71 kA
Power loss
at Rated Operating Conditions per Pole 1.6 W
Switches operating mechanism
Mechanism on Top of the Switch
Rated operational voltage
Main Circuit 750 V
Reach declaration
1SCC011021D0201
Poles description
3
Ul certificate
No certification needed
Environment
Atex certificate
No certification needed
Conventional free-air thermal current (ith)
Θ = 40 °C 40 A
Customs tariff number
85365080
Conventional thermal current (ithe)
Fully Enclosed 40 A
ETIM - 8
EC000216 - Switch disconnector
Etim 6
EC000216 - Switch disconnector
standards
IEC 60947-3
Etim 7
EC000216 - Switch disconnector
Etim 9
EC000216 - Switch disconnector (low voltage)
E-number (finland)
3601203
Rohs information
1SCC011020D0201
Vde certificate
No certification needed