All categories
Compare Cart

1SCA022497R0490 - OT40M3 - ABB

Expected in 2-4 weeks
1SCA022497R0490 - OT40M3 - ABB - OT40M3 - ABB - 0
1SCA022497R0490 - OT40M3 - ABB
12,88 €
12,88 € incl. VAT
Text About:
OT40M3 - ABB
12,88 €
SPECIFICATIONS
Additional Information
Data sheet, technical information 1SCC301020C0201
E-number (sweden) 2102720
Eclass V11.1 : 27371403
Package level 1 depth / length 103 mm
Product net depth / length 73
mm
Rohs status Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Special functions No
Weee category 5. Small Equipment (No External Dimension More Than 50 cm)
Main
Terminal type Screw Terminals
Mounting type Base mounting
degree of protection Front IP20
Complementary
Declaration of conformity - ce 1SCC301166D2703
Handle type Handle and shaft not included
Package level 1 gross weight 0.1 kg
Product net weight 0.09
kg
Conflict minerals reporting template (cmrt) 9AKK108467A5658
Etim 5 EC000216 - Switch disconnector
Package level 1 height 82 mm
Position of line terminals Top In - Bottom Out
Bottom In - Top Out
Product net width 35
mm
Cable cross section Cu 0.75 ... 10 mm²
Country of origin Finland (FI)
Distance between phases Standard
Package level 1 units box 1 piece
Lock type No
Package level 1 width 86 mm
tightening torque acc. IEC 60947-1 0.8 N·m
Environmental information 1SCC301262D0201
Instructions and manuals 1SCC301052M0006
Minimum order quantity 1 piece
mechanical durability 20000
Object classification code Q
Rated conditional short-circuit current (inc) (40 A fuse, ≤415V) 50 kA
(25 A fuse, 690 V) 50 kA
Package level 1 ean 6417019158402
Pollution degree 3
Product net height 68
mm
Rated short-time withstand current low voltage (icw) for 1 s 0.5 kA
Rated operational current ac-21a (ie) (380 ... 415 V) 40 A
Rated impulse withstand voltage (uimp) 8 kV
Rated operational current ac-22a (ie) (380 ... 415 V) 40 A
(500 V) 40 A
(690 V) 40 A
Rated insulation voltage (ui) acc. to IEC/EN 60664-1 750 V
Rated operational current ac-23a (ie) (380 ... 415 V) 23 A
(500 V) 23 A
(690 V) 12 A
Rated operational power ac-23a (pe) (220 ... 240 V) 5,5 kW
(400 ... 415 V) 11 kW
(500 V) 11 kW
(690 V) 11 kW
Operating mode Front operated
Rated short-circuit making capacity (icm) (690 V) 0.71 kA
Power loss at Rated Operating Conditions per Pole 1.6 W
Switches operating mechanism Mechanism on Top of the Switch
Rated operational voltage Main Circuit 750 V
Reach declaration 1SCC011021D0201
Poles description 3
Ul certificate No certification needed
Environment
Atex certificate No certification needed
Conventional free-air thermal current (ith) Θ = 40 °C 40 A
Customs tariff number 85365080
Conventional thermal current (ithe) Fully Enclosed 40 A
ETIM - 8 EC000216 - Switch disconnector
Etim 6 EC000216 - Switch disconnector
standards IEC 60947-3
Etim 7 EC000216 - Switch disconnector
Etim 9 EC000216 - Switch disconnector (low voltage)
E-number (finland) 3601203
Rohs information 1SCC011020D0201
Vde certificate No certification needed
Recently viewed
12,88 €
12,88 € incl. VAT
Expected in 2-4 weeks