Complementary
Ambient air temperature
Close to Contactor Fitted with Thermal O/L Relay -40 ... 70 °C
Close to Contactor without Thermal O/L Relay -40 ... 70 °C
Close to Contactor for Storage -60 ... +80 °C
Ccc certificate
CCC_2013010304646569
Declaration of conformity - ce
1SBD250000U1000
Package level 1 gross weight
1.29 kg
Product net weight
1.17
kg
Cad dimensional drawing
2CDC001079B0201
Etim 4
EC000066 - Magnet contactor, AC-switching
Etim 5
EC000066 - Magnet contactor, AC-switching
Package level 1 height
103 mm
Product net width
70
mm
[ics] rated service breaking capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 1150 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 750 A
Cb certificate
CB_SE-96557M2
Package level 1 units
box 1 piece
Connecting capacity control circuit
Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm²
Rigid Solid 1/2x 1 ... 2.5 mm²
Rigid Stranded 1/2x 1 ... 2.5 mm²
Package level 1 width
150 mm
Connecting capacity main circuit
Flexible with Ferrule 1/2x 6 ... 50 mm²
Flexible with Insulated Ferrule 1/2x 6 ... 50 mm²
Rigid Stranded 1x 6 ... 70 mm²
Rigid Stranded 2x 6 ... 50 mm²
Package level 2 depth / length
300 mm
Cqc certificate
CQC2013010304646569
Environmental information
1SBD250168E1000
1SBC100222M0201
Package level 2 gross weight
10.32 kg
Horsepower rating ul/csa
(120 V AC) Single Phase 7-1/2 hp
(200 ... 208 V AC) Three Phase 30 hp
(220 ... 240 V AC) Three Phase 40 hp
(240 V AC) Single Phase 20 hp
(440 ... 480 V AC) Three Phase 75 hp
(550 ... 600 V AC) Three Phase 75 hp
Package level 2 height
300 mm
Idea granular category code (igcc)
4758 >> Iec Contactors
Package level 2 units
box 8 piece
Instructions and manuals
1SBC101036M6801
Package level 2 width
250 mm
Package level 3 units
192 piece
Maximum operating altitude permissible
Without Derating 3000 m
Gl certificate
DNV-GL_TAE00001AF-3
Minimum order quantity
1 piece
Maximum mechanical switching frequency
3600 cycles per hour
wire stripping length
Main Circuit 17 mm
Number of main contacts no
3
Object classification code
Q
Package level 1 ean
3471523133242
Product net height
125.5
mm
Rated control circuit voltage (uc)
50 Hz 250 ... 500 V
60 Hz 250 ... 500 V
DC Operation 250 ... 500 V
Rated short-time withstand current low voltage (icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 840 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 140 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 300 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1200 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 450 A
Rated frequency (f)
Control Circuit 50 / 60 Hz
Main Circuit 50 / 60 Hz
Rated impulse withstand voltage (uimp)
8 kV
Mounting on din rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
Rated insulation voltage (ui)
acc. to IEC 60947-4-1 1000 V
acc. to UL/CSA 600 V
Rated operational current ac-1 (ie)
(690 V) 40 °C 130 A
(690 V) 60 °C 105 A
(690 V) 70 °C 90 A
Rated operational current ac-3 (ie)
(415 V) 60 °C 96 A
(440 V) 60 °C 96 A
(500 V) 60 °C 80 A
(690 V) 60 °C 57 A
(1000 V) 60 °C 30 A
(380 / 400 V) 60 °C 105 A
(220 / 230 / 240 V) 60 °C 105 A
Operate time
Between Coil De-energization and NC Contact Closing 19 ... 105 ms
Between Coil De-energization and NO Contact Opening 17 ... 100 ms
Between Coil Energization and NC Contact Opening 38 ... 95 ms
Between Coil Energization and NO Contact Closing 42 ... 100 ms
Rated operational power ac-3 (pe)
(415 V) 55 kW
(440 V) 55 kW
(500 V) 55 kW
(690 V) 55 kW
(1000 V) 40 kW
(380 / 400 V) 45 kW
(380 / 400 V) 55 kW
(220 / 230 / 240 V) 25 kW
(220 / 230 / 240 V) 30 kW
Rated operational current dc-1 (ie)
(110 V) 2 Poles in Series, 40 °C 130 A
(110 V) 2 Poles in Series, 60 °C 105 A
(110 V) 2 Poles in Series, 70 °C 90 A
(110 V) 3 Poles in Series, 40 °C 130 A
(110 V) 3 Poles in Series, 60 °C 105 A
(110 V) 3 Poles in Series, 70 °C 90 A
(220 V) 3 Poles in Series, 40 °C 125 A
(220 V) 3 Poles in Series, 60 °C 105 A
(220 V) 3 Poles in Series, 70 °C 90 A
(72 V) 1-Pole, 40 °C 130 A
(72 V) 1-Pole, 60 °C 105 A
(72 V) 1-Pole, 70 °C 90 A
(72 V) 2 Poles in Series, 40 °C 130 A
(72 V) 2 Poles in Series, 60 °C 105 A
(72 V) 2 Poles in Series, 70 °C 90 A
(72 V) 3 Poles in Series, 40 °C 130 A
(72 V) 3 Poles in Series, 60 °C 105 A
(72 V) 3 Poles in Series, 70 °C 90 A
Rated operational voltage
Main Circuit 1000 V
Reach declaration
2CMT2021-006202
Rated operational current dc-3 (ie)
(110 V) 2 Poles in Series, 40 °C 130 A
(110 V) 2 Poles in Series, 60 °C 105 A
(110 V) 2 Poles in Series, 70 °C 90 A
(110 V) 3 Poles in Series, 40 °C 130 A
(110 V) 3 Poles in Series, 60 °C 105 A
(110 V) 3 Poles in Series, 70 °C 90 A
(220 V) 3 Poles in Series, 40 °C 130 A
(220 V) 3 Poles in Series, 60 °C 105 A
(220 V) 3 Poles in Series, 70 °C 90 A
(72 V) 1-Pole, 40 °C 130 A
(72 V) 1-Pole, 60 °C 105 A
(72 V) 1-Pole, 70 °C 90 A
(72 V) 2 Poles in Series, 40 °C 130 A
(72 V) 2 Poles in Series, 60 °C 105 A
(72 V) 2 Poles in Series, 70 °C 90 A
(72 V) 3 Poles in Series, 40 °C 130 A
(72 V) 3 Poles in Series, 60 °C 105 A
(72 V) 3 Poles in Series, 70 °C 90 A
Resistance to shock acc
Closed, Shock Direction: A 25 g
Closed, Shock Direction: B1 25 g
Closed, Shock Direction: B2 15 g
Closed, Shock Direction: C1 25 g
Closed, Shock Direction: C2 25 g
Open, Shock Direction: B1 5 g
Rated operational current ac-3e (ie)
(415 V) 60 °C 96 A
(440 V) 60 °C 96 A
(500 V) 60 °C 80 A
(690 V) 60 °C 57 A
(380 / 400 V) 60 °C 105 A
(220 / 230 / 240 V) 60 °C 105 A
Rated operational current dc-5 (ie)
(110 V) 2 Poles in Series, 40 °C 130 A
(110 V) 2 Poles in Series, 60 °C 105 A
(110 V) 2 Poles in Series, 70 °C 90 A
(110 V) 3 Poles in Series, 40 °C 130 A
(110 V) 3 Poles in Series, 60 °C 105 A
(110 V) 3 Poles in Series, 70 °C 90 A
(220 V) 3 Poles in Series, 40 °C 130 A
(220 V) 3 Poles in Series, 60 °C 105 A
(220 V) 3 Poles in Series, 70 °C 90 A
(72 V) 1-Pole, 40 °C 130 A
(72 V) 1-Pole, 60 °C 105 A
(72 V) 1-Pole, 70 °C 90 A
(72 V) 2 Poles in Series, 40 °C 130 A
(72 V) 2 Poles in Series, 60 °C 105 A
(72 V) 2 Poles in Series, 70 °C 90 A
(72 V) 3 Poles in Series, 40 °C 130 A
(72 V) 3 Poles in Series, 60 °C 105 A
(72 V) 3 Poles in Series, 70 °C 90 A
Tightening torque ul/csa
Control Circuit 11 in·lb
Main Circuit 53 in·lb
Rated operational power ac-3e (pe)
(415 V) 55 kW
(440 V) 55 kW
(500 V) 55 kW
(690 V) 55 kW
(380 / 400 V) 45 kW
(380 / 400 V) 55 kW
(220 / 230 / 240 V) 25 kW
(220 / 230 / 240 V) 30 kW
Ul certificate
UL_20130301_E312527_14_1
Ul listing card
UL_E312527
Environment
Climatic withstand
Category B according to IEC 60947-1 Annex Q
Connecting capacity control circuit ul/csa
Rigid Solid 1/2x 18-14 AWG
Rigid Stranded 1/2x 18-14 AWG
Conventional free-air thermal current (ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 130 A
Customs tariff number
85364900
EAC certificate
EAC_RU_FRME77B03447
Rina certificate
RINA_ELE084013XG
Connecting capacity main circuit ul/csa
Rigid Stranded 1/2x 6-1 AWG
Declaration of conformity - ccc
2020980304001255
ETIM - 8
EC000066 - Power contactor, AC switching
Etim 6
EC000066 - Power contactor, AC switching
Rmrs certificate
RMRS_1802705280
Declaration of conformity - ukca
1SBD250031U1000
Etim 7
EC000066 - Power contactor, AC switching
General use rating ul/csa
(600 V AC) 115 A
Kc certificate
KC_HW02016-15011C
Lr certificate
LRS_1300087E1
E-number (finland)
3707138
Rohs information
2CMT2021-006277
Maximum electrical switching frequency
(AC-1) 600 cycles per hour
(AC-2 / AC-4) 150 cycles per hour
(AC-3) 1200 cycles per hour
Unspsc
39121529