Complementary
Ambient air temperature
Close to Contactor for Storage -60 ... +80 °C
Near Contactor for Operation in Free Air -40 ... 70 °C
Ccc certificate
CCC_2015010304824714
Declaration of conformity - ce
1SBD250001U1000
Package level 1 gross weight
1.27 kg
Product net weight
1.27
kg
Cad dimensional drawing
2CDC001079B0201
Etim 4
EC000066 - Magnet contactor, AC-switching
Etim 5
EC000066 - Magnet contactor, AC-switching
Package level 1 height
103 mm
Product net width
70
mm
[ics] rated service breaking capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 950 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 600 A
Cb certificate
CB_SE-108889A1
Package level 1 units
box 1 piece
Connecting capacity control circuit
Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm²
Rigid Solid 1/2x 1 ... 2.5 mm²
Rigid Stranded 1/2x 1 ... 2.5 mm²
Package level 1 width
150 mm
Connecting capacity main circuit
Flexible with Ferrule 1/2x 4 ... 35 mm²
Flexible with Insulated Ferrule 1/2x 4 ... 35 mm²
Rigid Stranded 1/2x 6 ... 35 mm²
Package level 2 depth / length
300 mm
Cqc certificate
CQC2015010304824714
Package level 2 gross weight
10.16 kg
Package level 2 height
300 mm
Idea granular category code (igcc)
4758 >> Iec Contactors
Package level 2 units
box 8 piece
Instructions and manuals
1SBC101047M6801
Package level 2 width
250 mm
Package level 3 units
192 piece
Maximum operating altitude permissible
Without Derating 3000 m
Gl certificate
DNV-GL_TAE00001AF-3
Minimum order quantity
1 piece
Maximum mechanical switching frequency
3600 cycles per hour
wire stripping length
Main Circuit 16 mm
Number of main contacts no
4
Object classification code
Q
Package level 1 ean
3471523133532
Product net height
125.5
mm
Rated control circuit voltage (uc)
50 Hz 100 ... 250 V
60 Hz 100 ... 250 V
DC Operation 100 ... 250 V
Rated short-time withstand current low voltage (icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 600 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 110 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 250 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1000 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 350 A
Rated frequency (f)
Control Circuit 50 / 60 Hz
Main Circuit 50 / 60 Hz
Rated impulse withstand voltage (uimp)
6 kV
Mounting on din rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
Rated insulation voltage (ui)
acc. to IEC 60947-4-1 690 V
acc. to UL/CSA 600 V
Rated operational current ac-1 (ie)
(690 V) 40 °C 70 A
(690 V) 60 °C 60 A
(690 V) 70 °C 50 A
Rated operational current ac-3 (ie)
(415 V) 60 °C 40 A
(440 V) 60 °C 40 A
(500 V) 60 °C 35 A
(690 V) 60 °C 25 A
(380 / 400 V) 60 °C 40 A
(220 / 230 / 240 V) 60 °C 40 A
Rated operational power ac-3 (pe)
(415 V) 22 kW
(440 V) 22 kW
(500 V) 22 kW
(690 V) 22 kW
(380 / 400 V) 18.5 kW
(220 / 230 / 240 V) 11 kW
Rated operational voltage
Main Circuit 690 V
Reach declaration
2CMT2021-006202
Ul certificate
UL_20141124-E312527-14-2
Ul listing card
UL_E312527
Environment
Climatic withstand
Category B according to IEC 60947-1 Annex Q
Connecting capacity control circuit ul/csa
Rigid Solid 1/2x 18-14 AWG
Rigid Stranded 1/2x 18-14 AWG
Conventional free-air thermal current (ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 105 A
Customs tariff number
85364900
EAC certificate
EAC_RU_FRME77B03447
Connecting capacity main circuit ul/csa
Rigid Stranded 1/2x 10-2 AWG
Declaration of conformity - ccc
2020980304001256
ETIM - 8
EC000066 - Power contactor, AC switching
Etim 6
EC000066 - Power contactor, AC switching
Rmrs certificate
RMRS_1400682124
Declaration of conformity - ukca
1SBD250032U1000
Etim 7
EC000066 - Power contactor, AC switching
General use rating ul/csa
(600 V AC) 60 A
Kc certificate
KC_HW02016-15009C
Lr certificate
LRS_1300087E1
E-number (finland)
3707257
Rohs information
2CMT2021-006277
Maximum electrical switching frequency
(AC-1) 600 cycles per hour
Unspsc
39121529