All categories
Compare Cart

1SBL281022R8010 - UA30-30-10 220-230V50HZ - ABB

Expected in 2-4 weeks
1SBL281022R8010 - UA30-30-10 220-230V50HZ - ABB - UA30-30-10 220-230V50HZ - ABB - 0
1SBL281022R8010 - UA30-30-10 220-230V50HZ - ABB
68,32 € excl. VAT
83,35 € incl. VAT
Text About:
UA30-30-10 220-230V50HZ - ABB
83,35 €
SPECIFICATIONS
Additional Information
Data sheet, technical information 1SBC101140C0203
Eclass V11.0 : 27371006
Package level 1 depth / length 115 mm
Product net depth / length 108.3
mm
Rohs status Following EU Directive 2011/65/EU
Mounting by screws (not supplied) 2 x M4 screws placed diagonally
Main
Terminal type Screw Terminals
degree of protection acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20
Complementary
Ambient air temperature Close to Contactor for Storage -60 ... +80 °C
Near Contactor for Operation in Free Air (0.85 ... 1.1 Uc) -40 ... +55 °C
Near Contactor for Operation in Free Air (Uc) -40 ... 70 °C
Ccc certificate CCC_2003010304060095
Declaration of conformity - ce 1SBD250805U1000
Package level 1 gross weight 0.71 kg
Product net weight 0.71
kg
Cad dimensional drawing 2CDC001079B0201
Etim 4 EC001079 - Capacitor magnet contactor
Etim 5 EC001079 - Capacitor magnet contactor
Package level 1 height 61 mm
Product net width 54
mm
[ics] rated service breaking capacity cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 820 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 340 A
Cb certificate CB_FR2880_60002378
Package level 1 units box 1 piece
Package level 1 width 101 mm
Connecting capacity main circuit Flexible with Cable End 2.5 ... 10 mm²
Rigid Cable 2.5 ... 16 mm²
Package level 2 depth / length 245 mm
Cqc certificate CQC2003010304060095


CQC2007010309256050
Environmental information 1SBD250028E1000
Package level 2 gross weight 17.04 kg
Package level 2 height 308 mm
Package level 2 units box 24 piece
Instructions and manuals FPTC407722P0001
Number of auxiliary contacts no 1
Package level 2 width 300 mm
Package level 3 units 576 piece
Maximum operating altitude permissible Without Derating 3000 m
Minimum order quantity 1 piece
Maximum mechanical switching frequency 3600 cycles per hour
mechanical durability 10 million
Number of main contacts no 3
Object classification code Q
Package level 1 ean 3471522074805
Product net height 90
mm
Rated operational power ac-6b (pe) (230 / 240 V) 40 °C, 50 / 60 Hz 16 kvar
(230 / 240 V) 55 °C, 50 / 60 Hz 16 kvar
(230 / 240 V) 70 °C, 50 / 60 Hz 11 kvar
(400 / 415 V) 40 °C, 50 / 60 Hz 27.5 kvar
(400 / 415 V) 70 °C, 50 / 60 Hz 19 kvar
(400 / 415 V) 55 °C, 50 / 60 Hz 27.5 kvar
(440 V) 40 °C, 50 / 60 Hz 30 kvar
(440 V) 55 °C, 50 / 60 Hz 30 kvar
(440 V) 70 °C, 50 / 60 Hz 20 kvar
(500 / 550 V), 40 °C, 50 / 60 Hz 34 kvar
(500 / 550 V) 55 °C, 50 / 60 Hz 34 kvar
(500 / 550 V) 70 °C, 50 / 60 Hz 23.5 kvar
(690 V) 40 °C, 50 / 60 Hz 45 kvar
(690 V) 55 °C, 50 / 60 Hz 45 kvar
(690 V) 70 °C, 50 / 60 Hz 32 kvar
Rated control circuit voltage (uc) 50 Hz 220 ... 230 V
60 Hz 230 ... 240 V
Rated frequency (f) Auxiliary Circuit 50 / 60 Hz
Control Circuit 50 / 60 Hz
Rated impulse withstand voltage (uimp) 8 kV
Mounting on din rail TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Rated insulation voltage (ui) acc. to IEC 60947-4-1 1000 V
acc. to IEC 60947-5-1 690 V
acc. to UL/CSA 600 V
Operate time Between Coil De-energization and NO Contact Opening 4 ... 11 ms
Between Coil Energization and NO Contact Closing 8 ... 21 ms
Rated operational current ac-15 (ie) (500 V) 2 A
(690 V) 2 A
(24 / 127 V) 6 A
(220 / 240 V) 4 A
(380 / 400 V) 3 A
Rated operational current dc-13 (ie) (24 V) 6 / 144 A
(48 V) 2.8 / 134 A
(72 V) 2 / 144 A
(125 V) 1.1 / 138 A
(250 V) 0.55 / 138 A
Rated operational voltage Auxiliary Circuit 690 V
Main Circuit 690 V
Reach declaration 2CMT2021-006202
Ul certificate UL-US-L312527-4104-71017991-2


UL-CA-L312527-4104-71017991-2
Environment
Climatic withstand acc. to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 specification II
Coil consumption Average Holding Value 50 / 60 Hz 12 V·A
Average Pull-in Value 50 Hz 120 V·A
Average Pull-in Value 60 Hz 120 V·A
Holding at Max. Rated Control Circuit Voltage 50 Hz 12 V·A
Holding at Max. Rated Control Circuit Voltage 50 Hz 3 W
Holding at Max. Rated Control Circuit Voltage 60 Hz 12 V·A
Holding at Max. Rated Control Circuit Voltage 60 Hz 3 W
Pull-in at Max. Rated Control Circuit Voltage 50 Hz 120 V·A
Pull-in at Max. Rated Control Circuit Voltage 60 Hz 140 V·A
Connecting capacity auxiliary circuit Flexible with Cable End 0.75 ... 2.5 mm²
Rigid Cable 1 ... 4 mm²
Connecting terminals (delivered in open position) main poles M 5 (+,-) pozidriv 2 screw with 2x (5.6x6.5 mm) connector
Conventional free-air thermal current (ith) acc. to IEC 60947-5-1, Θ = 40 °C 16 A
Customs tariff number 85364900
Declaration of conformity - ccc 2020980304001610


2020980304001216
ETIM - 8 EC001079 - Capacitor contactor
Etim 6 EC001079 - Capacitor contactor
Gost certificate GOST_POCCFRME77B07175
Short-circuit protective devices Auxiliary Circuit - gG Type Fuses 10 A
gG Type Fuses 1.5 ... 1.8 A
Declaration of conformity - ukca 1SBD250822U1000
Etim 7 EC001079 - Capacitor contactor
E-number (finland) 3709173
Rohs information 2CMT2021-006277
Unspsc 39121529
Recently viewed
68,32 € excl. VAT
83,35 € incl. VAT
Expected in 2-4 weeks