Complementary
Actuator type
Rotary Handle
Ambient air temperature
Operation -20 ... +70 °C
Storage -50 ... +80 °C
Declaration of conformity - ce
1SAD938505-0051
Package level 1 gross weight
2.3 kg
Product net weight
2.269
kg
Etim 4
EC000074 - Motor protective circuit-breaker
Etim 5
EC000074 - Motor protective circuit-breaker
Package level 1 height
171 mm
Product net width
70
mm
[ics] rated service breaking capacity
(230 V AC) 100 kA
(400 V AC) 25 kA
(440 V AC) 20 kA
(500 V AC) 4 kA
(690 V AC) 3 kA
Ambient air temperature compensation
No
Package level 1 units
1 piece
Package level 1 width
76.5 mm
tightening torque
Main Circuit 4 ... 6 N·m
Connecting capacity main circuit
Flexible with Ferrule 1x 2.5 ... 50 mm²
Flexible with Ferrule 2x 2.5 ... 35 mm²
Solid 1/2x 2.5 ... 16 mm²
Stranded 1x 10 ... 70 mm²
Stranded 2x 10 ... 50 mm²
Contact position indication
ON / OFF / TRIP
Horsepower rating ul/csa
(200 V AC) Three Phase 30 Hp
(208 V AC) Three Phase 30 Hp
(220 ... 240 V AC) Three Phase 30 Hp
(440 ... 480 V AC) Three Phase 75 Hp
(550 ... 600 V AC) Three Phase 100 Hp
Idea granular category code (igcc)
4845 >> 3 Pole Motor Circuit Protector Circuit Breakers
Instructions and manuals
1SAM507001R1001
Maximum operating altitude permissible
2000 m
Maximum operating voltage ul/csa
Main Circuit 600 V AC
Minimum order quantity
1 piece
wire stripping length
Main Circuit 17 mm
mechanical durability
50000 cycle
Object classification code
F
electrical durability
25000 cycle
Package level 1 ean
4013614265716
Pollution degree
3
Product net height
165
mm
mounting position
1 ... 6
Rated frequency (f)
Main Circuit 50 Hz
Main Circuit 60 Hz
Rated impulse withstand voltage (uimp)
Main Circuit 6 kV
Mounting on din rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Rated insulation voltage (ui)
690 V
Rated operational current ac-3 (ie)
90 A
Power loss
at Rated Operating Conditions per Pole 10 W
Rated operational power ac-3 (pe)
(400 V) Three Phase 45 kW
Rated operational voltage
Main Circuit 690 V AC
Main Circuit 450 V DC
Rated instantaneous short-circuit current setting (ii)
1170 A
Poles description
3
Recommended screw driver
Hexagon 4
Rated operational current (ie)
90 A
Resistance to shock acc
11 ms Pulse 25g
Tightening torque ul/csa
Main Circuit 35 ... 53 in·lb
Ul certificate
UL_E167205
Rated ultimate short-circuit breaking capacity (icu)
(230 V AC) 100 kA
(400 V AC) 50 kA
(440 V AC) 50 kA
(500 V AC) 8 kA
(690 V AC) 5 kA
Setting range
None
Environment
Conventional free-air thermal current (ith)
Main Circuit 90 A
Customs tariff number
85362090
EAC certificate
1SAA937001-2703
Connecting capacity main circuit ul/csa
Flexible 1x 10-2/0 AWG
Flexible 1/2x 10-1/0 AWG
Stranded 1x 10-2/0 AWG
Stranded 1/2x 10-1/0 AWG
Cul certificate
1SAA937000-1701
Declaration of conformity - ccc
2022960307001586
ETIM - 8
EC000074 - Motor protection circuit-breaker
Etim 6
EC000074 - Motor protection circuit-breaker
Rmrs certificate
1SAA918000-0704
standards
CSA 22.2 No. 14
IEC/EN 60947-1
IEC/EN 60947-2
IEC/EN 60947-4-1
UL 508
Declaration of conformity - ukca
1SAD938500-1051
Etim 7
EC000074 - Motor protection circuit-breaker
General use rating ul/csa
(600 V AC) 90 A
Dnv certificate
1SAA937000-0301
Rohs information
1SAD938505-0051
Unspsc
39121521