All categories
Compare Cart

1SAM550000R1010 - MS495-100 - ABB

Expected in 2-4 weeks
1SAM550000R1010 - MS495-100 - ABB - MS495-100 - ABB - 0
1SAM550000R1010 - MS495-100 - ABB
incl. VAT
Text About:
MS495-100 - ABB
SPECIFICATIONS
Additional Information
Bv certificate 1SAA937000-0202
Data sheet, technical information 1SBC100173C0201
E-number (sweden) 3112270
Eclass V11.0 : 27370401
Package level 1 depth / length 190 mm
Product net depth / length 174
mm
Rohs status Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Main
Terminal type Screw Terminals
degree of protection Housing IP20
Main Circuit Terminals IP00
Complementary
Actuator type Rotary Handle
Ambient air temperature Operation -20 ... +70 °C
Operation Compensated -20 ... +60 °C
Storage -50 ... +80 °C
Declaration of conformity - ce 1SAD938506-0050
Package level 1 gross weight 2.3 kg
Product net weight 2.295
kg
Etim 4 EC000074 - Motor protective circuit-breaker
Etim 5 EC000074 - Motor protective circuit-breaker
Package level 1 height 171 mm
Product net width 70
mm
[ics] rated service breaking capacity (230 V AC) 100 kA
(400 V AC) 25 kA
(440 V AC) 20 kA
(500 V AC) 4 kA
(690 V AC) 3 kA
Ambient air temperature compensation Yes
Package level 1 units 1 piece
Package level 1 width 76.5 mm
tightening torque Main Circuit 4 ... 6 N·m
Connecting capacity main circuit Flexible with Ferrule 1x 2.5 ... 50 mm²
Flexible with Ferrule 2x 2.5 ... 35 mm²
Solid 1/2x 2.5 ... 16 mm²
Stranded 1x 10 ... 70 mm²
Stranded 2x 10 ... 50 mm²
Cqc certificate CQC2013010307604042
Contact position indication ON / OFF / TRIP
Horsepower rating ul/csa (200 V AC) Three Phase 30 Hp
(208 V AC) Three Phase 30 Hp
(220 ... 240 V AC) Three Phase 40 Hp
(440 ... 480 V AC) Three Phase 75 Hp
(550 ... 600 V AC) Three Phase 100 Hp
Idea granular category code (igcc) 4845 >> 3 Pole Motor Circuit Protector Circuit Breakers
Instructions and manuals 1SAM507001R1001
Maximum operating altitude permissible 2000 m
Maximum operating voltage ul/csa Main Circuit 600 V AC
Gl certificate 1SAA937000-0404
Minimum order quantity 1 piece
wire stripping length Main Circuit 17 mm
Instructions and manuals (part 2) 2CDC131017M5701
mechanical durability 50000 cycle
Object classification code F
electrical durability 25000 cycle
Package level 1 ean 4013614265488
Pollution degree 3
Product net height 165
mm
mounting position 1 ... 6
Rated frequency (f) Main Circuit 50 Hz
Main Circuit 60 Hz
Rated impulse withstand voltage (uimp) Main Circuit 6 kV
Mounting on din rail TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Rated insulation voltage (ui) 690 V
Rated operational current ac-3 (ie) 100 A
Power loss at Rated Operating Conditions per Pole 3.5 ... 5.4 W
Rated operational power ac-3 (pe) (400 V) Three Phase 55 kW
Rated operational voltage Main Circuit 690 V AC
Main Circuit 450 V DC
Rated instantaneous short-circuit current setting (ii) 1235 A
Poles description 3
Recommended screw driver Hexagon 4
Rated operational current (ie) 100 A
Resistance to shock acc 11 ms Pulse 25g
Tightening torque ul/csa Main Circuit 35 ... 53 in·lb
Ul certificate UL_E167205


UL_E195536
Rated ultimate short-circuit breaking capacity (icu) (230 V AC) 100 kA
(400 V AC) 50 kA
(440 V AC) 50 kA
(500 V AC) 8 kA
(690 V AC) 5 kA
Setting range 80 ... 100 A
Time-current characteristic curve 1SAM500501F0010
Environment
Atex certificate 1SAA937000-3901
Conventional free-air thermal current (ith) Main Circuit 100 A
Customs tariff number 85362090
EAC certificate 1SAA937001-2703
Connecting capacity main circuit ul/csa Flexible 1x 10-2/0 AWG
Flexible 1/2x 10-1/0 AWG
Stranded 1x 10-2/0 AWG
Stranded 1/2x 10-1/0 AWG
Cul certificate cUL_E195536
Data sheet, technical information (part 3) 9AKK105713A1102
Declaration of conformity - ccc 2022960307001586
ETIM - 8 EC000074 - Motor protection circuit-breaker
Etim 6 EC000074 - Motor protection circuit-breaker
Rmrs certificate 1SAA918000-0704
standards CSA 22.2 No. 14
IEC/EN 60947-1
IEC/EN 60947-2
IEC/EN 60947-4-1
UL 508
Declaration of conformity - ukca 1SAD938500-1050
Etim 7 EC000074 - Motor protection circuit-breaker
General use rating ul/csa (600 V AC) 99 A
Dnv certificate 1SAA937000-0302
Lr certificate 1SAA937000-0504
E-number (finland) 3707078
Rohs information 1SAD938506-0050
Unspsc 39121521
Recently viewed
incl. VAT
Expected in 2-4 weeks