Complementary
Actuator type
Rotary Handle
Ambient air temperature
Operation -25 ... +60 °C
Operation Compensated -25 ... +60 °C
Storage -50 ... +80 °C
Declaration of conformity - ce
1SAD101100-3409
Package level 1 gross weight
1.1 kg
Product net weight
0.97
kg
Cad dimensional drawing
2CDC001079B0201
Etim 5
EC000074 - Motor protective circuit-breaker
Package level 1 height
155 mm
Product net width
55
mm
[ics] rated service breaking capacity
(230 V AC) 100 kA
(250 V DC) 3 Poles in Series 100 kA
(400 V AC) 100 kA
(440 V AC) 50 kA
(500 V AC) 30 kA
(690 V AC) 10 kA
Ambient air temperature compensation
No
Cb certificate
1SAA918002-2002
Package level 1 units
box 1 piece
Package level 1 width
78 mm
tightening torque
Main Circuit 4 N·m
Connecting capacity main circuit
Flexible with Ferrule 1/2x 1 ... 35 mm²
Flexible with Insulated Ferrule 1/2x 1 ... 35 mm²
Flexible 1/2x 1 ... 35 mm²
Rigid 1/2x 1 ... 4 mm²
Solid 1/2x 1 ... 4 mm²
Stranded 1/2x 1 ... 50 mm²
dimension
1SAM400402F0001
Package level 2 depth / length
400 mm
Package level 2 ean
4013614504013
Cqc certificate
CQC2015010307760141
Contact position indication
ON / OFF / TRIP
Environmental information
1SAC200051H0009
Package level 2 gross weight
13 kg
Horsepower rating ul/csa
(200 V AC) Three Phase 7.5 Hp
(208 V AC) Three Phase 10 Hp
(220 ... 240 V AC) Three Phase 10 Hp
(440 ... 480 V AC) Three Phase 20 Hp
(550 ... 600 V AC) Three Phase 30 Hp
Package level 2 height
320 mm
Idea granular category code (igcc)
4731 >> Manual Starters
Package level 2 units
carton 12 piece
Dnv gl certificate
1SAA963002-0301
Instructions and manuals
2CDC131082M6801
Package level 2 width
330 mm
Maximum operating altitude permissible
2000 m
Maximum operating voltage ul/csa
Main Circuit 600 V AC
Full load amps motor use
(200 V AC) Three Phase 25.3 A
(208 V AC) Three Phase 30.8 A
(220 ... 240 V AC) Three Phase 28 A
(440 ... 480 V AC) Three Phase 27 A
(550 ... 600 V AC) Three Phase 32 A
Minimum order quantity
1 piece
Iecex certificate
1SAA918000-4001
wire stripping length
Main Circuit 16 mm
Instructions and manuals (part 2)
2CDC131060M0202
mechanical durability
50000 cycle
Object classification code
F
electrical durability
25000 cycle
Locked rotor amps
(200 V AC) Three Phase 146 A
(208 V AC) Three Phase 179 A
(220 ... 240 V AC) Three Phase 162 A
(440 ... 480 V AC) Three Phase 145 A
(550 ... 600 V AC) Three Phase 174 A
Package level 1 ean
4013614486159
Pollution degree
3
Product net height
142.65
mm
Minimum mounting distance
Electrical Conductive Board, Horizontal - Up to 1000 V 1.5 mm
Electrical Conductive Board, Horizontal - Up to 400 V 0 mm
Electrical Conductive Board, Horizontal - Up to 690 V 1.5 mm
Electrical Conductive Board, Vertical 75 mm
Other Device Same Type, Horizontal 0 mm
Other Device Same Type, Vertical 150 mm
mounting position
1 ... 6
Rated frequency (f)
Main Circuit 50 Hz
Main Circuit 60 Hz
Rated impulse withstand voltage (uimp)
Main Circuit 8 kV
Mounting on din rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Rated insulation voltage (ui)
1000 V
Rated operational current ac-3 (ie)
32 A
Power loss
4.4 W
Rated operational power ac-3 (pe)
(400 V) Three Phase 15 kW
Rated operational voltage
Main Circuit 690 V AC
Main Circuit 250 V DC
Rated instantaneous short-circuit current setting (ii)
480 A
Reach declaration
1SAA960005-4502
Poles description
3
Recommended screw driver
Pozidriv 2
Rated operational current (ie)
32 A
Resistance to shock acc
11 ms Pulse 25g
Rated operational current ac-3e (ie)
32 A
Rated operational current dc-5 (ie)
32 A
Tightening torque ul/csa
Main Circuit 35 in·lb
Rated operational power ac-3e (pe)
(400 V) Three Phase 15 kW
Ul certificate
E137861-20150206
E345003-20150206
Rated ultimate short-circuit breaking capacity (icu)
(230 V AC) 100 kA
(250 V DC) 100 kA
(400 V AC) 100 kA
(440 V AC) 50 kA
(500 V AC) 30 kA
(690 V AC) 10 kA
Setting range
None
Short-circuit current rating (sccr)
Manual Self-Protected Combination Controllers (Type E), (480Y / 277 V AC) 65 kA
Manual Self-Protected Combination Controllers (Type E), (600Y / 347 V AC) 30 kA
Any UL Listed Fuses or Circuit-Breakers, Group Installations (480 V AC) 65 kA
Any UL Listed Fuses or Circuit-Breakers, Group Installations (600 V AC) 30 kA
Any UL Listed Fuses or Circuit-Breakers, Motor Disconnect (480 V AC) 65 kA
Any UL Listed Fuses or Circuit-Breakers, Motor Disconnect (600 V AC) 30 kA
Any UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (480Y / 277 V AC) 65 kA
Any UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (600Y / 347 V AC) 30 kA
Time-current characteristic curve
1SAM400515F0001
Environment
Conventional free-air thermal current (ith)
Main Circuit 32 A
Customs tariff number
85362010
EAC certificate
1SAA963000-2701
Connecting capacity main circuit ul/csa
Flexible 1/2x 16-0 AWG
Stranded 1/2x 16-0 AWG
Declaration of conformity - ccc
2020980307003042
ETIM - 8
EC000074 - Motor protection circuit-breaker
Etim 6
EC000074 - Motor protection circuit-breaker
Rmrs certificate
1SAA918000-0704
standards
CSA 22.2 No. 14
IEC/EN 60947-1
IEC/EN 60947-2
IEC/EN 60947-4-1
UL 60947-4-1
Declaration of conformity - ukca
1SAD201100-3409
Etim 7
EC000074 - Motor protection circuit-breaker
General use rating ul/csa
(600 V AC) 32 A
Lr certificate
1SAA918001-0501
E-number (finland)
3707294
Rohs information
1SAA963006-4502
Unspsc
39121521