Complementary
Actuator type
Rotary Handle
Ambient air temperature
Around the Enclosure 0 ... +40 °C
Operation -25 ... +70 °C
Operation Compensated -25 ... +60 °C
Storage -50 ... +80 °C
Declaration of conformity - ce
1SAD101100-3404
Package level 1 gross weight
0.23 kg
Product net weight
0.215
kg
Cad dimensional drawing
2CDC001079B0201
Etim 4
EC000228 - Power circuit-breaker for trafo/generator/installation prot.
Etim 5
EC000228 - Power circuit-breaker for trafo/generator/installation prot.
Package level 1 height
50 mm
Product net width
45
mm
[ics] rated service breaking capacity
(230 V AC) 100 kA
(400 V AC) 100 kA
Ambient air temperature compensation
Yes
Package level 1 units
box 1 piece
Package level 1 width
92 mm
tightening torque
Main Circuit 0.8 ... 1.2 N·m
Connecting capacity main circuit
Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 1/2x 0.75 ... 2.5 mm²
Flexible 1/2x 0.75 ... 2.5 mm²
Rigid 1/2x 1 ... 4 mm²
dimension
1SAM300402F0001
Package level 2 depth / length
395 mm
Package level 2 ean
4013614487118
Cqc certificate
CQC2010010307387700
Contact position indication
ON / OFF / TRIP
Environmental information
1SAC200049H0009
Package level 2 gross weight
9.586 kg
Package level 2 height
210 mm
Idea granular category code (igcc)
4864 >> Enclosed 3 Pole Circuit Breakers
Package level 2 units
carton 40 piece
Instructions and manuals
2CDC131057M6801
Package level 2 width
280 mm
Maximum operating altitude permissible
2000 m
Maximum operating voltage ul/csa
Main Circuit 600 V AC
Full load amps motor use
(120 V AC) Single Phase 0.16 A
(220 ... 240 V AC) Single Phase 0.16 A
Minimum order quantity
1 piece
wire stripping length
Main Circuit 9 mm
Instructions and manuals (part 2)
2CDC131060M0202
mechanical durability
100000 cycle
Object classification code
F
electrical durability
50000 cycle
Locked rotor amps
(120 V AC) Single Phase 0.96 A
(220 ... 240 V AC) Single Phase 0.96 A
Package level 1 ean
4013614484919
Pollution degree
3
Product net height
90
mm
Minimum mounting distance
Electrical Conductive Board, Vertical 75 mm
Other Device Same Type, Horizontal 9 mm
Other Device Same Type, Vertical 150 mm
mounting position
1 ... 6
Rated frequency (f)
Main Circuit 50 Hz
Main Circuit 60 Hz
Rated impulse withstand voltage (uimp)
Main Circuit 6 kV
Mounting on din rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Rated insulation voltage (ui)
690 V
Power loss
at Rated Operating Conditions per Pole 0.6 ... 1.5 W
Rated operational voltage
Main Circuit 690 V AC
Rated instantaneous short-circuit current setting (ii)
3.2 A
Reach declaration
1SAA963005-4502
Poles description
3
Recommended screw driver
Pozidriv 2
M3.5
Rated operational current (ie)
0.16 A
Resistance to shock acc
11 ms Pulse 25g
Tightening torque ul/csa
Main Circuit 10 ... 12 in·lb
Ul certificate
E137861-20090225
Rated ultimate short-circuit breaking capacity (icu)
(400 V AC) 100 kA
Setting range
0.10 ... 0.16 A
Short-circuit current rating (sccr)
Any UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (480Y / 277 V AC) 65 kA
Any UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (600Y / 347 V AC) 47 kA
Time-current characteristic curve
1SAM300535F0001
Environment
Conventional free-air thermal current (ith)
Main Circuit 0.16 A
Customs tariff number
85362010
Connecting capacity main circuit ul/csa
Flexible 1/2x 16-12 AWG
Stranded 1/2x 16-12 AWG
Declaration of conformity - ccc
2020980307003526
ETIM - 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Etim 6
EC000228 - Power circuit-breaker for trafo/generator/installation prot.
Rmrs certificate
1SAA918000-0704
standards
IEC/EN 60947-1
IEC/EN 60947-2
IEC/EN 60947-4-1
Declaration of conformity - ukca
1SAD201100-3404
Etim 7
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Kc certificate
1SAA963002-1502
E-number (finland)
3707265
Rohs information
1SAA963006-4502
Unspsc
39121601