Complementary
Ambient air temperature
Operation -25 ... +55 °C
Storage -40 ... +80 °C
Declaration of conformity - ce
1SAD938506-0302
Package level 1 gross weight
0.23 kg
Product net weight
0.225
kg
Cad dimensional drawing
2CDC001079B0201
Etim 5
EC001653 - Installation contactor for distribution board
Package level 1 height
69.5 mm
Product net width
36
mm
Cb certificate
1SAA920004-2001
Package level 1 units
1 piece
Connecting capacity control circuit
Flexible with Ferrule 1x 1 ... 2.5 mm²
Flexible with Ferrule 2x 0.75 ... 1 mm²
Flexible with Insulated Ferrule 1x 1 ... 2.5 mm²
Flexible with Insulated Ferrule 2x 0.75 ... 1 mm²
Flexible 1x 1 ... 4.0 mm²
Flexible 2x 1 ... 2.5 mm²
Rigid 1x 1 ... 4 mm²
Rigid 2x 1 ... 2.5 mm²
Package level 1 width
92 mm
tightening torque
Control Circuit 0.9 N·m
Main Circuit 1 N·m
Connecting capacity main circuit
Flexible with Ferrule 1x 1.5 ... 10 mm²
Flexible with Ferrule 2x 1.5 ... 2.5 mm²
Flexible with Insulated Ferrule 1x 1.5 ... 10 mm²
Flexible with Insulated Ferrule 2x 1.5 mm²
Flexible 1x 1.5 ... 10 mm²
Flexible 2x 1.5 ... 4 mm²
Rigid 1x 1.5 ... 10 mm²
Rigid 2x 1.5 ... 4 mm²
Package level 2 depth / length
395 mm
Package level 2 ean
4013614538612
Cqc certificate
CQC2017010304993564
CQC2017010304993565
Environmental information
1SAC200063H0009
Package level 2 gross weight
11.5 kg
Horsepower rating ul/csa
(220 ... 240 V AC) Single Phase, NO 1 Hp
(440 ... 480 V AC) Single Phase, NO 2 Hp
Package level 2 height
210 mm
Idea granular category code (igcc)
4759 >> Installation contactor for distribution board
Package level 2 units
48 piece
Instructions and manuals
2CDC103043M6801
Package level 2 width
280 mm
Maximum operating altitude permissible
2000 m
Maximum operating voltage ul/csa
Main Circuit 480 V AC
Minimum order quantity
1 piece
wire stripping length
Control Circuit 7 mm
Main Circuit 10 mm
mechanical durability
1000000 cycle
Number of main contacts no
2
Object classification code
Q
electrical durability
AC-1 (NO) 130000 cycle
AC-3 (NO) 500000 cycle
AC-7a (NO) 130000 cycle
AC-7b (NO) 500000 cycle
Package level 1 ean
4013614524219
Pollution degree
3
Product net height
85
mm
Rated control circuit voltage (uc)
230 V
Rated frequency (f)
Control Circuit 400 Hz
Control Circuit 50 Hz
Control Circuit 60 Hz
Control Circuit DC
Main Circuit 50 Hz
Main Circuit 60 Hz
Main Circuit DC
Rated impulse withstand voltage (uimp)
6 kV
Rated insulation voltage (ui)
500 V
Rated operational current ac-1 (ie)
(NO) 25 A
Rated operational current ac-3 (ie)
(230 V) Single Phase, NO 9 A
Rated operational current ac-7a (ie)
(NO) 25 A
Rated operational current ac-7b (ie)
(230 V) Single Phase, NO 9 A
Rated operational power ac-1 (pe)
(230 V) Single Phase, NO 5.8 kW
Rated operational power ac-3 (pe)
(230 V) Single Phase, NO 1.3 kW
Rated operational power ac-7a (pe)
(230 V) Single Phase, NO 5.8 kW
Rated operational power ac-7b (pe)
(230 V) Single Phase, NO 1.3 kW
Rated operational voltage
Main Circuit 220 V DC
Main Circuit 400 V AC
Reach declaration
2CMT2021-006202
Poles description
2
Recommended screw driver
Control Circuit Pozidriv 1
Main Circuit Pozidriv 1
Resistance to shock acc
11 ms Pulse 15g
Tightening torque ul/csa
Control Circuit 8 in·lb
Main Circuit 9 in·lb
Ul certificate
E191658-19960301
Environment
Connecting capacity control circuit ul/csa
Solid 16-10 AWG
Stranded 16-10 AWG
Customs tariff number
85365080
EAC certificate
1SAA920001-2702
Rina certificate
1SAA920000-0801
Connecting capacity main circuit ul/csa
Solid 16-8 AWG
Stranded 16-8 AWG
Declaration of conformity - ccc
2020980304001312
2020980304001314
ETIM - 8
EC001653 - Installation contactor for distribution board
Etim 6
EC001653 - Installation contactor for distribution board
Rmrs certificate
1SAA920000-0705
standards
IEC/EN 60947-1
IEC/EN 60947-4-1
IEC/EN 61095
UL 60947-1
UL 60947-4-1
Declaration of conformity - ukca
1SAD938501-1302
Etim 7
EC001653 - Installation contactor for distribution board
Width in number of modular spacings
2
Dnv certificate
1SAA920000-0306
Rohs information
2CMT2021-006277
Unspsc
39121529