Main
name of the device
Vigi NG125
type of product or equipment
Blocs différentiels Vigi
differential sensitivity
300 mA
1000 mA
500 mA
3000 mA
[ui] rated insulation voltage
690 V CA 50/60 Hz se conformer à CEI 60947-2
Complementary
9 mm pitches
11
[ue] rated operational voltage
440...500 V CA 50/60 Hz
electrical connection on circuit breaker
Par vis
tightening torque
6 N.m
[uimp] rated impulse withstand voltage
8 kV se conformer à CEI 60947-2
in rated operational current
125 A
product weight
0,8 kg
electrical life
10000 cycle se conformer à CEI 60947-2
connection mode
Borne du type à cage10…50 mm² souple
Borne du type à cage16…70 mm² rigide
width (w)
207 mm
network frequency
50/60 Hz
delay
Réglable instantané/sélectif/retardé
position of the switchgear in the installation
Départ
wire stripping length
20 mm
differential technology
Indépendant de la tension
mounting bracket
Rail DIN symétrique 35 mm
Network type
Type A
Poles description
4P
Environment
degree of pollution
3 se conformer à CEI 60947-2
ip degree of protection
IP40 conforming to CEI 60947-2
operating altitude
2000 m
electromagnetic compatibility
Tenue aux ondes 8/20 µs, 5000 A se conformer à CEI 60947-2
standards
CEI 60947-2
relative humidity
95 % à 55 °C
tropicalization
2 se conformer à CEI 60068-1