Main
Group of channels
2 groups of 4 outputs
Complementary
[ue] rated operational voltage
120 V AC
Product certifications
CSA
FM Class 1 Division 2
UL
response time
1/2 x 1/f (= 0.5 of one line cycle) from state 0 to state 1
1/2 x 1/f (= 0.5 of one line cycle) from state 1 to state 0
Handle front plate colour
141.5 mm
maximum leakage current
1.9 mA 120 V AC
Product or component type
Discrete output base AC
Current consumption
125 mA at 120 V AC
maximum voltage drop
<1.5 V 2 A at state 1
current per channel
2 A
marking
CE
minimum output current
5 mA
Discrete output current
4 A per group
8 A per module
width (w)
125 mm
Local signalling
8 LEDs for channel status
Net weight
0.32 kg
Discrete output type
Triac
Discrete output voltage
120 V AC
Isolation between channels and bus
1780 V AC for 1 minute
Discrete output number
8
Power dissipation
7.5 W maximum
6 W typical
depth
47.5 mm
Output overload protection
Internal fuse
Surge current
10 A for 2 cycles
15 A for 1 cycle
5 A for 3 cycles
Resistance to electrostatic discharge
4 kV contact conforming to IEC 801-2
8 kV on air conforming to IEC 801-2
Terminals description plc n°1
(4)OUT_DIS#4
(2)OUT_DIS#2
(1)OUT_DIS#1
(3)OUT_DIS#3
(1L+)PW
TB
(5)OUT_DIS#5
(6)OUT_DIS#6
(1N)PW
(7)OUT_DIS#7
(8)OUT_DIS#8
Resistance to electromagnetic fields
10 V/m 80...1000 MHz conforming to IEC 801-3
Short-circuit protection
Internal fuse, 5 A slow-blow per group
Environment
Ambient air temp for storage/transportation
-40…85 °C
operating altitude
<= 5000 m
Range of product
Modicon Momentum automation platform
ambient air temperature for operation
0…60 °C
relative humidity
95 % without condensation
protective treatment
TC