Main
Group of channels
2 groups of 16 outputs
Complementary
[ue] rated operational voltage
24 V DC
Product certifications
CSA
UL
response time
0.1 ms from state 0 to state 1
0.1 ms from state 1 to state 0
Handle front plate colour
141.5 mm
maximum leakage current
1 mA 24 V DC
Product or component type
Discrete output base DC
Current consumption
250 mA at 24 V DC
maximum voltage drop
<0.5 V 0.5 A at state 1
current per channel
0.5 A
marking
CE
Discrete output current
16 A per module
8 A per group
width (w)
125 mm
Local signalling
32 LEDs for channel status
Net weight
0.21 kg
Discrete output type
Solid state switch
Discrete output voltage
24 V DC
Isolation between channels and bus
500 V AC
Discrete output number
32
Power dissipation
6 W typical
7.5 W maximum
depth
47.5 mm
Output overload protection
Outputs electronically protected
Surge current
5 A during 1 ms
Resistance to electrostatic discharge
4 kV contact conforming to IEC 801-2
8 kV on air conforming to IEC 801-2
Terminals description plc n°1
(15)OUT_DIS#15
TB
(2)OUT_DIS#2
(8)OUT_DIS#8
(L+)PW_POS
(16)OUT_DIS#16
(7)OUT_DIS#7
(M-)PW_NEG
(12)OUT_DIS#12
(9)OUT_DIS#9
(11)OUT_DIS#11
(14)OUT_DIS#14
(1)OUT_DIS#1
(5)OUT_DIS#5
(10)OUT_DIS#10
(13)OUT_DIS#13
(3)OUT_DIS#3
(4)OUT_DIS#4
(6)OUT_DIS#6
Terminals description plc n°2
(6)OUT_DIS#22
(4)OUT_DIS#20
(7)OUT_DIS#23
(2L+)PW_POS
(3)OUT_DIS#19
TB_1
(8)OUT_DIS#24
(10)OUT_DIS#26
(12)OUT_DIS#28
(2)OUT_DIS#18
(13)OUT_DIS#29
(16)IN_DIS#32
(11)OUT_DIS#27
(14)OUT_DIS#30
(15)OUT_DIS#31
(5)OUT_DIS#21
(9)OUT_DIS#25
(1)OUT_DIS#17
(1L+)PW_POS
Resistance to electromagnetic fields
10 V/m 80...1000 MHz conforming to IEC 801-3
Short-circuit protection
Outputs electronically protected
Environment
Ambient air temp for storage/transportation
-40…85 °C
operating altitude
<= 5000 m
Range of product
Modicon Momentum automation platform
ambient air temperature for operation
0…60 °C
relative humidity
95 % without condensation
protective treatment
TC