Complementary
Product certifications
UL
CSA
response time
1/2 x 1/f from state 0 to state 1 on input
1/2 x 1/f from state 0 to state 1 on output
1/2 x 1/f from state 1 to state 0 on input
1/2 x 1/f from state 1 to state 0 on output
Handle front plate colour
141.5 mm
maximum leakage current
1.3 mA at 120 V (output circuit)
Product or component type
Discrete triac I/O base AC
[us] rated supply voltage
120 V AC
Current consumption
160 mA at 120 V AC
maximum voltage drop
<1.5 V 0.5 A at state 1 output circuit
current state 0 guaranteed
<= 2.6 mA
marking
CE
current state 1 guaranteed
>= 6 mA
Discrete output current
2 A per group
4 A per module
30 mA...0.5 A per point
Discrete input logic
Positive
width (w)
125 mm
Input resistance
4 kOhm
input voltage limits
74...132 V
network frequency
47...63 Hz
Discrete input voltage
120 V AC
Discrete input number
10 conforming to IEC 1131-2 Type 2
Net weight
0.22 kg
Discrete output type
Triac
Discrete output voltage
120...132 V DC
Isolation between channels and bus
1780 V AC
voltage state 1 guaranteed
> 74 V
Discrete output number
8
Power dissipation
<= 8 W
6 W
depth
47.5 mm
voltage state 0 guaranteed
< 20 V
Operating rate
3000 cyc/h 0.5 A inductive
Resistance to electrostatic discharge
4 kV contact conforming to IEC 801-2
8 kV on air conforming to IEC 801-2
Terminals description plc n°1
(8)IN_DIS#8
(5)IN_DIS#5
(9)IN_DIS#9
(4)IN_DIS#4
(10)IN_DIS#10
(3)IN_DIS#3
(L1)PW
(N)PW
(6)IN_DIS#6
(7)IN_DIS#7
(1)IN_DIS#1
TB
(2)IN_DIS#2
Terminals description plc n°2
(3)OUT_DIS#3
(6)OUT_DIS#6
(1N)PW
(2)OUT_DIS#2
(1L1)PW
(8)OUT_DIS#8
(7)OUT_DIS#7
(1)OUT_DIS#1
(4)OUT_DIS#4
(5)OUT_DIS#5
TB_1
Resistance to electromagnetic fields
10 V/m 80...1000 MHz conforming to IEC 801-3
Protection type
Internal 2 x 2.5 A slow-blow fuses
Environment
Ambient air temp for storage/transportation
-40…85 °C
operating altitude
<= 5000 m
Range of product
Modicon Momentum automation platform
ambient air temperature for operation
0…60 °C
relative humidity
95 % without condensation
protective treatment
TC