Complementary
Product certifications
CSA
UL
response time
< 0.1 ms from state 0 to state 1 on output
< 0.1 ms from state 1 to state 0 on output
0.06 ms from state 0 to state 1 on input
0.08 ms from state 1 to state 0 on input
Handle front plate colour
141.5 mm
maximum leakage current
1 mA at 24 V (output circuit)
Product or component type
Discrete solid state I/O base DC
[us] rated supply voltage
24 V DC
Current consumption
250 mA at 24 V DC
maximum voltage drop
<0.5 V 0.5 A at state 1 output circuit
current state 0 guaranteed
<= 1.2 mA
marking
CE
current state 1 guaranteed
>= 2.5 mA
Discrete output current
4 A per group
8 A per module
0.5 A per point
Discrete input logic
Positive
width (w)
125 mm
Input resistance
4 kOhm
input voltage limits
- 3...30 V
Discrete input voltage
24 V DC
Discrete input number
16 conforming to IEC 1131-2 Type 1
Net weight
0.2 kg
Discrete output type
Solid state switch
Discrete output voltage
<= 30 V DC
24 V DC
Fault type
Overload on output
Isolation between channels and bus
500 V AC
voltage state 1 guaranteed
11...30 V
Discrete output number
16
Power dissipation
<= 8 W
6 W
depth
47.5 mm
voltage state 0 guaranteed
-3...5 V
Peak output current
5 A
Resistance to electrostatic discharge
4 kV contact conforming to IEC 801-2
8 kV on air conforming to IEC 801-2
Terminals description plc n°1
(6)IN_DIS#6
(1)IN_DIS#1
(4)IN_DIS#4
(8)IN_DIS#8
(14)IN_DIS#14
(L+)PW_POS
(10)IN_DIS#10
(3)IN_DIS#3
(M-)PW_NEG
(12)IN_DIS#12
(16)IN_DIS#16
(9)IN_DIS#9
(11)IN_DIS#11
(5)IN_DIS#5
TB
(2)IN_DIS#2
(15)IN_DIS#15
(7)IN_DIS#7
(13)IN_DIS#13
Terminals description plc n°2
(16)OUT_DIS#16
TB_1
(12)OUT_DIS#12
(13)OUT_DIS#13
(4)OUT_DIS#4
(2)OUT_DIS#2
( 10)OUT_DIS#10
(15)OUT_DIS#15
(5)OUT_DIS#5
(6)OUT_DIS#6
(11)OUT_DIS#11
(1L+)PW_POS!@ !(9)OUT_DIS#9
(1)OUT_DIS#1
(14)OUT_DIS#14
(2L+)PW_POS
(7)OUT_DIS#7
(8)OUT_DIS#8
(3)OUT_DIS#3
Resistance to electromagnetic fields
10 V/m 80...1000 MHz conforming to IEC 801-3
Environment
Ambient air temp for storage/transportation
-40…85 °C
operating altitude
<= 5000 m
Range of product
Modicon Momentum automation platform
ambient air temperature for operation
0…60 °C
relative humidity
95 % without condensation
protective treatment
TC