Main
Thermocouple type
Thermocouple E
Thermocouple S
Thermocouple K
Thermocouple N
Thermocouple B
Thermocouple R
Thermocouple J
Thermocouple T
reverse polarity protection
Internal
Complementary
Absolute accuracy error
+/- 21 µV 25 °C +/- 25 mV
+/- 27 µV 25 °C +/- 100 mV
+/- 46 µV 60 °C +/- 25 mV
+/- 94 µV 60 °C +/- 100 mV
Product certifications
FM Class 1 Division 2
CSA
UL
Analogue input range
+/- 100 mV 15 bits + sign > 10000 kOhm
+/- 25 mV 15 bits + sign > 10000 kOhm
data formats
Full 16 bits signed
Handle front plate colour
125 mm
Product or component type
Analogue input base
Current consumption
305 mA at 24 V DC
Associated fuse rating
500 mA, fast blow
marking
CE
Analogue input number
4
Common mode rejection
120 dB DC between channels
130 dB 50 Hz AC between channels
135 dB DC between channels to ground
140 dB 60 Hz AC between channels
145 dB 50 Hz AC between channels to ground
155 dB 60 Hz AC between channels to ground
maximum power dissipation in w
5.5 W
Analogue input type
Differential
width (w)
141.5 mm
Local signalling
4 LEDs for channel status
External power requirement
+/- 30 V DC
Net weight
0.215 kg
Isolation between channels
400 V DC
Isolation between channels and ground
500 V AC for 1 minute
depth
47.5 mm
Isolation between supply and ground
500 V for 1 minute
electrical connection
2 connectors for removable terminal blocks
Permissible common mode voltage
100 V DC between channels to ground
115 V AC single or three phases between channels
200 V DC between channels
250 V AC between channels to ground
250 V AC single phase between channels
update time
500 ms
Resistance to electrostatic discharge
4 kV contact conforming to IEC 801-2
8 kV on air conforming to IEC 801-2
Serial mode rejection
35 dB 50 Hz AC
45 dB 60 Hz AC
Resistance to electromagnetic fields
10 V/m 80...1000 MHz conforming to IEC 801-3
Temperature probe type
Ni 100 0.125 mA +/- 25 mV
Ni 1000 0.125 mA +/- 100 mV
Pt 100 0.125 mA +/- 25 mV
Pt 1000 0.125 mA +/- 100 mV
Protection type
Internal 2 A slow-blow
Environment
Ambient air temp for storage/transportation
-40…85 °C
operating altitude
<= 5000 m
Range of product
Modicon Momentum automation platform
ambient air temperature for operation
0…60 °C
relative humidity
95 % without condensation
protective treatment
TC