Main
type of filter
Low pass input filter 10 kHz
reverse polarity protection
Internal
Complementary
Absolute accuracy error
+/- 0.15 % of full scale 25 °C +/- 10 V
+/- 0.15 % of full scale 25 °C +/- 5 V
+/- 0.25 % full scale 25 °C 4...20 mA
+/- 0.25 % full scale 60 °C +/- 10 V
+/- 0.25 % full scale 60 °C +/- 5 V
+/- 0.45 % full scale 60 °C 4...20 mA
Product certifications
UL
CSA
FM Class 1 Division 2
Analogue input range
4...20 mA 12 bits + sign < 0.25 Ohm
+/- 10 V 12 bits + sign > 2200 kOhm
+/- 5 V 12 bits + sign > 2200 kOhm
data formats
Full 16 bits signed
Handle front plate colour
125 mm
Product or component type
Analogue input base
Current consumption
305 mA at 24 V DC
Associated fuse rating
500 mA, fast blow
marking
CE
Analogue input number
16
maximum power dissipation in w
5.55 W
Analogue input type
Single ended
width (w)
141.5 mm
Local signalling
16 LEDs for channel status
temperature drift
+/- 30 % full scale +/- 10 V 60 °C
+/- 30 % full scale +/- 5 V 60 °C
+/- 60 % full scale 4...20 mA 60 °C
External power requirement
+/- 30 V DC
Net weight
0.215 kg
Isolation between channels and ground
1780 V AC for 1 minute
depth
47.5 mm
Isolation between supply and ground
500 V for 1 minute
electrical connection
2 connectors for removable terminal blocks
Permissible common mode voltage
100 V 47...63 Hz DC between channels to ground
250 V 47...63 Hz AC between channels to ground
update time
25 ms
Resistance to electrostatic discharge
4 kV contact conforming to IEC 801-2
8 kV on air conforming to IEC 801-2
Resistance to electromagnetic fields
10 V/m 80...1000 MHz conforming to IEC 801-3
Protection type
Internal 2 A slow-blow
Environment
Ambient air temp for storage/transportation
-40…85 °C
operating altitude
<= 5000 m
Range of product
Modicon Momentum automation platform
ambient air temperature for operation
0…60 °C
relative humidity
95 % without condensation
protective treatment
Conformal coating Humiseal 1A33
TC