Main
Device short name
VLT
Range
PowerLogic
scale
0-500 V
device mounting
Flush
Complementary
range compatibility
Prisma (Prisma P) door
Prisma (Prisma G) door
Handle front plate colour
72 mm
Product or component type
Voltmeter
accuracy class
Class 1.5
type of measurement
Voltage
Overload withstand
1.2 Un, permanently
2 Un, 5 s
width (w)
72 mm
temperature drift
+/- 0.003 %/°C
Operating position
30°/vertical
Mounting support
Front face
depth
75 mm
Power consumption in va
3 VA
Technology type
Ferromagnetic
Scale type
62 mm over 90°
Environment
ip degree of protection
IP52
Reference temperature
23 °C
ambient air temperature for operation
-25…50 °C
standards
IEC 61010-1
IEC 60051-1
IEC 61000-4