Main
calorimetric heat release nfpa 130 (astm e 1354)
28 MJ/kg
catalog page
Page 506 (C-1-2017)
flammability rating according to ul 94
V0
insulating material
PA
fire protection for rail vehicles (din en 45545-2) r22
HL 1 - HL 3
relative insulation material temperature index (elec., ul 746 b)
130 °C
fire protection for rail vehicles (din en 45545-2) r23
HL 1 - HL 3
gtin
4017918002299
number of rows
1
Product type
Ground terminal block
fire protection for rail vehicles (din en 45545-2) r24
HL 1 - HL 3
item number
0443052
fire protection for rail vehicles (din en 45545-2) r26
HL 1 - HL 3
nominal cross section
16 mm²
packing unit
50 pc
product key
BE1251
insulating material group
I
weight per piece (excluding packing)
35.606 g
weight per piece (including packing)
35.606 g
smoke gas toxicity nfpa 130 (smp 800c)
passed
specific optical density of smoke nfpa 130 (astm e 662)
passed
static insulating material application in cold
-60 °C
surface flammability nfpa 130 (astm e 162)
passed
temperature index of insulation material (din en 60216-1 (vde 0304-21))
130 °C
Complementary
maximum power dissipation for nominal condition
2.43 W
open side panel
No
height ns 32
52 mm
height ns 35/7,5
47 mm
number of connections
2
rated surge voltage
6 kV
terminal block mounting
1.5 Nm ... 1.8 Nm (PE foot with mounting screw, M4)
conductor cross section, flexible [awg]
12 ... 6 (converted acc. to IEC)
Country of origin
DE
height ns 35/15
54.5 mm
length [l]
42.5 mm
conductor cross section, rigid [awg]
2.5 mm² ... 25 mm²
Handle front plate colour
1.85 "
tightening torque
1.5 ... 1.8 Nm
connection in acc. with standard
IEC 60947-7-2
cross section awg
12 ... 3 (converted acc. to IEC)
conductor cross section flexible, with ferrule without plastic sleeve
1.5 mm² ... 16 mm²
flexible conductor cross section (ferrule with plastic sleeve)
1.5 mm² ... 16 mm²
grounding foot
Yes
note
Please observe the current carrying capacity of the DIN rails.
number of connections per level
2
width (w)
12 mm
screw thread
M4
Colour
green-yellow
stripping length
11 mm
Minimum order quantity
1 pc
Environment
Ambient air temp for storage/transportation
-25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
Ambient air temperature for installation
-5 °C ... 70 °C
ambient temperature (actuation)
-5 °C ... 70 °C
china rohs
Environmentally friendly use period: unlimited = EFUP-e
Customs tariff number
85369010
eclass-11.0
27141141
Specifications - Environmental Product Compliance:
No hazardous substances above threshold values
ambient air temperature for operation
-60 °C ... 105 °C (max. short-term operating temperature RTI Elec.)
ETIM - 8
EC000901
overvoltage category
III
reach svhc
4-Nonylphenol, branched and linear
permissible humidity (storage/transport)
30 % ... 70 %
unspsc 21.0
39121400