Additional Information
connection capacity awg
24 ... 14
general
When aligning with a feed-through terminal block with the same shape, an end cover must be interposed with insulation voltages of > 690 V
connection capacity flexible
0.2 mm² ... 2.5 mm²
connection capacity rigid
0.2 mm² ... 4 mm²
identification
II 2 GD Ex eb IIC Gb
output
(Permanent)
rated cross section awg
14
torque range
0.6 Nm ... 0.8 Nm
torque range for pe foot
0.5 Nm ... 0.6 Nm
Main
calorimetric heat release nfpa 130 (astm e 1354)
28 MJ/kg
catalog page
Page 463 (C-1-2019)
number of positions
1
flammability rating according to ul 94
V0
insulating material
PA
fire protection for rail vehicles (din en 45545-2) r22
HL 1 - HL 3
relative insulation material temperature index (elec., ul 746 b)
130 °C
fire protection for rail vehicles (din en 45545-2) r23
HL 1 - HL 3
gtin
4017918002169
number of rows
1
Product type
Ground terminal block
fire protection for rail vehicles (din en 45545-2) r24
HL 1 - HL 3
item number
0441083
fire protection for rail vehicles (din en 45545-2) r26
HL 1 - HL 3
nominal cross section
2.5 mm²
packing unit
50 pc
product key
BE1221
insulating material group
I
weight per piece (excluding packing)
17.15 g
weight per piece (including packing)
17.899 g
smoke gas toxicity nfpa 130 (smp 800c)
passed
specific optical density of smoke nfpa 130 (astm e 662)
passed
static insulating material application in cold
-60 °C
surface flammability nfpa 130 (astm e 162)
passed
temperature index of insulation material (din en 60216-1 (vde 0304-21))
130 °C
Complementary
maximum power dissipation for nominal condition
0.77 W
open side panel
No
height ns 32
52 mm
height ns 35/7,5
47 mm
number of connections
2
rated surge voltage
8 kV
terminal block mounting
0.5 Nm ... 0.6 Nm (PE foot with mounting screw, M2.5)
conductor cross section, flexible [awg]
24 ... 14 (converted acc. to IEC)
Country of origin
TR
height ns 35/15
54.5 mm
length [l]
42.5 mm
conductor cross section, rigid [awg]
0.2 mm² ... 4 mm²
Handle front plate colour
1.85 "
tightening torque
0.6 ... 0.8 Nm
connection in acc. with standard
IEC 60947-7-2
cross section awg
24 ... 12 (converted acc. to IEC)
conductor cross section flexible, with ferrule without plastic sleeve
0.25 mm² ... 2.5 mm²
flexible conductor cross section (ferrule with plastic sleeve)
0.25 mm² ... 1.5 mm²
grounding foot
Yes
note
Please observe the current carrying capacity of the DIN rails.
number of connections per level
2
width (w)
5.2 mm
screw thread
M3
Colour
green-yellow
stripping length
8 mm
Minimum order quantity
50 pc
Environment
Ambient air temp for storage/transportation
-25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
Ambient air temperature for installation
-5 °C ... 70 °C
ambient temperature (actuation)
-5 °C ... 70 °C
china rohs
Environmentally friendly use period: unlimited = EFUP-e
Customs tariff number
85369010
degree of pollution
3
eclass-11.0
27141141
Specifications - Environmental Product Compliance:
No hazardous substances above threshold values
ambient air temperature for operation
-60 °C ... 105 °C (max. short-term operating temperature RTI Elec.)
ETIM - 8
EC000901
overvoltage category
III
reach svhc
4-Nonylphenol, branched and linear
operating temperature range
-60 °C ... 110 °C
permissible humidity (storage/transport)
30 % ... 70 %
unspsc 21.0
39121400